This Clamp-on Ground Resistance Tester is used on multi-grounded systems without disconnecting the ground under test. Simply clamps around the ground conductor or rod and measures the resistance to ground fast and accurately. By performing measurements on intact ground systems, the user also verifies the quality of the grounding connections and bonds. Resistance and continuity of grounding loops around pads and buildings may also be measured.
This AEMC 3711 Clamp-on Ground Resistance Tester includes a current measurement function. The probe’s high sensitivity enables measurement of leakage current flowing to ground or circulating in ground loops down to 1mA and neutral and phase currents to 30Arms. This feature provides additional information which is vital in distribution ground networks carrying higher levels of noise and harmonics that affect power quality.
Applications:
- Measure electrical ground rod and grid resistance
- Use on multi-grounded systems without disconnecting the ground rod under test
- Measure resistance and continuity of grounding loops around pads and buildings
- Measure leakage current flowing to ground or circulating in ground systems
- Conduct field surveys and retrieve and analyze readings at a later time
- Use on cell towers and telecommunication sites
- Use on pools, spas and other consumer installations
For greater capabilities see the AEMC 3731 Clamp-on Ground Resistance Tester
What's Included:
- Hard carrying case
- 9V Alkaline battery
- 25½ calibration check loop
- And user manual

The Bad:
The Bottom Line:
Full Review
- Simple and fast clamp-on operation - no leads, no auxiliary rods or spacing requirements. No need to disconnect neutral service
- Direct reading of ground resistance from 0.01Ω to 1200Ω
- Direct reading of continuity and ground loop resistance
- Direct reading of ground leakage or phase current from 1mA to 30Arms
- Jaw design with large 1.25" (32mm) window - accommodates up to 1000MCM cables
- Auto-off for power management
- CE Mark and UL approved
- Rugged Lexan head and body construction resists breakage
- Patented design
|
ELECTRICAL |
|
||||||||
|
|
|
Auto-Ranging 0.01Ω
to 1200Ω |
|||||||
|
Range |
0.10 to
1.00Ω |
1.0 to
50.0Ω |
50.0 to
100.0Ω |
100 to 200Ω
|
200 to 400Ω
|
400 to 600Ω
|
600 to
1200Ω |
||
|
Resolution
|
0.01Ω |
0.1Ω |
0.5Ω |
1Ω |
5Ω |
10Ω |
50Ω |
||
|
Accuracy
|
±2% of Reading ± 0.02Ω |
±1.5% of Reading ± 0.1Ω |
±2% of Reading ± 0.5Ω |
±3% of Reading ± 1Ω |
±6% of Reading ± 10Ω |
±10% of Reading ± 10Ω |
Approx. 25% of Reading ± 50Ω |
||
|
|
Auto-Ranging 1mA to
30.00Arms |
||||||||
|
Range |
1 to 299mA |
0.300 to 2.999A |
3.00 to 29.99A |
||||||
|
Resolution
|
1mA |
0.001A |
0.01A |
||||||
|
Accuracy
|
±2.5% of |
±2.5% of |
±2.5% of |
||||||
|
Resistance
Measurement Frequency |
2403Hz |
||||||||
|
Resistance
Overload |
OL displayed above 1200Ω |
||||||||
|
Current
Measurement Frequency |
47 to 800Hz |
||||||||
|
Current
Overload |
OL displayed above 29.99Arms |
||||||||
|
Power
Source |
9V Alkaline battery (IEC 6LF22 or
NEDA 1604A) |
||||||||
|
|
Typical: 8 hours or approx. 1000
measurements of 30 seconds |
||||||||
|
MECHANICAL |
|
||||||||
|
Display |
3 3/4 Digit, 1.73 x 1.10" (44
x 28mm) |
||||||||
|
Operating
Temperature |
14° to 131°F (-10° to 55°C) |
||||||||
|
Storage
Temperature |
-22° to 158°F (-30° to 70°C) |
||||||||
|
Relative
Humidity |
10 to 90% RH @ 14° to 104°F (-10°
to 40°C), 75% RH @ 131°F (55°C) |
||||||||
|
Dimensions
|
9.25 x 3.94 x 2.17" (235 x
100 x 55mm) |
||||||||
|
Weight |
2.2 lbs (1kg) |
||||||||
|
Jaw
Window Diameter |
1.25" (32mm) |
||||||||
|
Jaw
Opening |
1.38" (35mm) |
||||||||
|
Case |
Lexan® 920A or equivalent (UL94V2)
|
||||||||
|
Colors |
Gray body, red jaws |
||||||||
|
Shock
Test |
IEC 68-2-27 |
||||||||
|
Vibration
Test |
IEC 68-2-6 |
||||||||
|
Drop
Test (1m) |
IEC 68-2-32 |
||||||||
|
Dielectric
Test |
2500VAC |
||||||||
|
Environmental
|
IP30, IEC 359, Group III |
||||||||
|
Working
Voltage |
150V, Cat. III – Pollution Degree
2; 300V, Cat. II – Pollution Degree 2 |
||||||||
|
Max Overload (A or ½ Function) |
100A continuous, 200A (< 5s)
50/60Hz |
||||||||
|
|
No. 362,639 |
||||||||
|
UL File
No. |
E192383 |
||||||||
|
SAFETY |
|
||||||||
|
Safety
Rating |
EN 61010-2-032 (Class 2) Double
Insulation |
||||||||
|
CE Mark |
Yes |
||||||||


Yes! Available up to 